iC60 - A9F74370

IC60N - miniature circuit breaker - 3P - 0.5A - C curve

 

Main
device application Distribution
range Acti 9
product name Acti 9 iC60
product or component type Miniature circuit-breaker
device short name IC60N
poles description 3P
number of protected poles 3
[In] rated current 0.5 A
network type AC
DC

trip unit technology Thermal-magnetic
curve code C
breaking capacity 50 kA Icu conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
50 kA Icu conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
50 kA Icu conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz
50 kA Icu conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz
25 kA Icu conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
6000 A Icn conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz
10 kA Icu conforming to EN/IEC 60947-2 - <= 180 V DC

utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2

suitability for isolation Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
Yes conforming to EN 60898-1
Yes conforming to IEC 60898-1

standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2

quality labels NF
Complementary
network frequency 50/60 Hz
magnetic tripping limit 8 x In +/- 20 %
[Ics] rated service breaking capacity 6000 A 100 % x Icu conforming to IEC 60898-1 - 400 V AC 50/60 Hz
10 kA 100 % x Icu conforming to IEC 60947-2 - 125...180 V DC
10 kA 100 % x Icu conforming to EN 60947-2 - 125...180 V DC
6000 A 100 % x Icu conforming to EN 60898-1 - 400 V AC 50/60 Hz
50 kA 100 % x Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
50 kA 100 % x Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
50 kA 100 % x Icu conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
25 kA 100 % x Icu conforming to EN 60947-2 - 440 V AC 50/60 Hz
50 kA 100 % x Icu conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz
25 kA 100 % x Icu conforming to IEC 60947-2 - 440 V AC 50/60 Hz
50 kA 100 % x Icu conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz
50 kA 100 % x Icu conforming to EN 60947-2 - 12...133 V AC 50/60 Hz

limitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1

[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60947-2
500 V AC 50/60 Hz conforming to EN 60947-2

[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2

contact position indicator Yes
control type Toggle
local signalling Trip indicator
mounting mode Fixed
mounting support DIN rail
comb busbar and distribution block compatibility YES top or bottom
9 mm pitches 6
height 85 mm
width 54 mm
depth 78.5 mm
product weight 0.375 kg
colour White
mechanical durability 20000 cycles
electrical durability 10000 cycles
connections - terminals Single terminal, top or bottom rigid wire(s) 1...25 mm² max
Single terminal, top or bottom flexible wire(s) 1...16 mm² max

wire stripping length 14 mm top or bottom
tightening torque 2 N.m top or bottom
earth-leakage protection Separate block